1、使用维护说明书T4120高位消防水箱目录directory1.设备名称与型号Equipment name and model number2.用途与适用范围Purpose and scope of application3.技术参数、结构形式与工作原理Technical parameters, structure and working principle3.1总体The overall3.2主要部件1Main part 13.3主要部件2Main part 24.设备的安装和调试Equipment installation and debugging5.操作和使用Operation and
2、use 6.维护保养与故障排除Maintenance and troubleshooting6.1设备的维护和保养Equipment maintenance and maintenance6.1.1日常维护和保养The daily maintenance and maintenance6.1.2 定期维护和保养Regular maintenance and maintenance6.2设备常见故障与处理办法Equipment mon faults and processing methods6.2.1 机械元部件常见故障A mon failure of mechanical ponents7.
3、附件The attachment罐体结构图Structure of tank1.设备名称与型号Equipment name and model number设备名称:高位消防水箱规格型号:750020001500mm.Device name: high fire water tank Specifications:7500*2000*1500mm.2.用途与适用范围Purpose and scope of application高位消防水箱用于储存消防用水,水箱为方形平底封闭贮箱,箱体顶部焊一圈加强筋,箱内作加强处理;配就地显示液位计;顶部开人孔并加盖板,同时配置箱内爬梯.high fire
4、water tank used to store fire water, square flat closed tank, water tank for system.after the weld a ring stiffeners, in strengthening treatment; With local display liquid level meter; At the top of the open manhole and top cover plate, and at the same time the gym in the cabinet.3.技术参数Technical par
5、ameters3.1总体overall技术规范表:Technical specification sheet:项目project单位unit数据备注note设备台数Equipment sets台1设备尺寸equipment sizemm7500*2000*1500设备容积volumem318设计压力Design pressure0.1Mpa运行压力Operatingpressure常压运行温度Operating temperature常温normal temperature材质materialSS304技术要求:高位消防水箱为SS304不锈钢材质焊接的方形水箱.分片交货;需在国内开料、打坡口按
6、标准、成型、涂底漆,分类包装,分片规格按设备制造图的规定进行.高位消防水箱本体上设人孔一个,并配扶梯; 液位计选用玻璃管就地显示液位计;本体设有下列接口:进水、溢流、出水、呼吸、排污与备用接口.Technical requirements:high fire water tank for SS304 stainless steel welding square tank. Fragmentation of delivery; Needs to open the door at home, a groove , molding, primer, classification of packagi
7、ng, shard specifications in accordance with the provisions of the equipment manufacture drawing. high fire water tank manhole a is set on ontology, and escalators;level gauge glass tube in situ show that the level;body is equipped with the following interface: water, Mouth breathing, flooding, water
8、, sewage, and the standby interface.工作原理:贮存消防用水,高位消防水箱指符合规范要求的静压满足最不利点消火栓水压的水箱,利用重力自流供水,设置在建筑的最高处,静压不能满足最不利点消火栓水压时,应设增压稳压设施.临时高压消防给水系统必须设置消防水箱,系统平时仅能满足消防水压而不能保证消防用水量.发生火灾时,通过启动消防水泵提供灭火用水量.Working principle:Storage fire water, high fire water tank refers to conform to the requirements of the specific
9、ation of static pressure to meet the most unfavorable point of fire hydrant water pressure tank, using gravity artesian water, installed in the building, the highest point of static pressure can not meet the most unfavorable point fire hydrant water pressure, should set pressure regulated facilities
10、. Temporary high-pressure fire water system must be set fire water tank, usually can only meet the fire water system and cannot ensure fire water consumption. A fire, the fire flow through start the fire pump.3.2主要部件13.2 main part1高位消防水箱high fire water tank1本体ontology外形尺寸:Overall dimensions:7500*200
11、0*15000有效容积Effective volume:18m3材质:SS304Material:SS304台 set12UPVC液位计UPVC level gauge玻璃管液位计:DN25Glass tube liquid level Meter:DN25个Set13进水口Water inletDN50,PN1.0个Set14溢流口overflow mouthDN100,PN1.0个Set15出水口outletDN150,PN1.0个Set16排污口drainDN100,PN1.0个Set17手动阀液位计配套Supporting manual valve DN25,PN1.0个Set28备用